Part Number Hot Search : 
AZ3266X FR104 T111019 USD170 IDTQS H0010 PST3134 SD1553C
Product Description
Full Text Search
 

To Download EDS11-132B Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  specifications 1. control and computation functions control and computation functions are implemented by combining function-software packages called "wafers." combination of wafers is called "wafer connection." cc-m comprises 100 kinds of wafers. wafer connection is made by operating the keys on the front panel or using the pc based configurator. ( 1) pid control ?number of loops and pid : selectable among the following 1 loop (1 control output / 2pid) 2 loops (2 control outputs / 4pid) 4 loops (4 control outputs / 8pid) ?proportional band (p) : 1.0 to 3276.7%, set at 3000.0% for de- livery ?integration time (i) : 0.1 to 3276.7 s, set at 3000.0 s for deliv- ery ?derivative time (d) : 0.0 to 900.0 s, set at 0.0 s for delivery (2) programming function ?programming method : wafer connection ?program capacity : 48 wafers x 4 loops (max. 192 wa- fers) a maximum of 48 wafers usable in 1 loop ?kind of wafer : 100 kinds listed in table 1 compact controller m [cc-m] (programmable continuous output type) digital controller the compact controller m (programmable continuous out- put type) is a multi-loop process controller. it accepts 1 to 5 v dc and signals from thermocouples and resistance bulb as input, and is provided with abundant con- trol and computation functions to allow configuring a flex- ible system with a high cost performance. features 1. multi-loop controller of up to 4 control outputs. cc-m has max.4 control outputs,that is real 4-loop multi- loop controller. [note] in this data sheet, the term "loop" is used in the same meaning as the quantity of control output. 2. control and computation functions dependent on wafers control and computation functions are implemented by combining function-software packages called "wafers." since the wafers are built in the controller, optimum system can be programmed by using the front-panel keys and the pc based configurator. 3. high visibility ensured with color graphic display a color lcd is adopted for graphic display of multi-loop bar graph and trend screens,etc. 4. communication function (option) fuji plc link (t-link) are available. 5. back-up (option) if the controller becomes faulty, influence over the sys- tem can be evaded by changing the built-in backup opera- tion unit. 6. memory card (option) memory card can save any data, for example process in- put, wafer output, etc. data sheet pda2 date EDS11-132B july 15, 2005
pda2 2 (3) computation cycle : 200 ms for 4-loop (8pid) control of sim- plicity pid (4) alarm function ?method : alarm can be displayed and output through wafer connection. ?kinds : each high/low of pv, sv and mv, pv change rate alarm, mv change rate alarm, high/low deviations. 2. input signals performance under reference condition (23 2?c, 55 10%rh, 100 v to 240 v ac, 50/60hz power supply frequency or 24 v dc power supply voltage, free from vibration and the effect of external noise) 2-1 analog input signal ?number of inputs screw terminal ; 7 inputs compression terminal ; 8 inputs ?inpute signal types : dc voltage, dc current, thermocouple (option), resistance bulb (option) two thermocouple inputs or two resis- tance bulb inputs are selectable. (1) dc voltage / dc current input range: selectable among 0 to 5 v dc, 1 to 5 v dc and 0 to 10 v dc initial set before delivery : 1 to 5 v dc input accuracy: 0.1% of input span 1 digit scaling (engineering data conversion) : settable within a range from -32767 to 32767 4, 3, 2, 1 or 0 digit below decimal point is selectable. initial set before delivery : 0.00% to 100.00% engineering unit: settable in up to 8 characters usable characters: alphabets numerals, symbols such as +, , * ,etc. input accuracy guarantee range: 5% to 105% of input range. however, minus inputs are excluded. ? aximum continuous permissible volt- age: 35 v input resistance: 1 m ? or more influence by ambient temperature: 0.1% fs/10 c or less. influence by power supply fluctuation: 0.1% fs or less. isolation : non-isolated from internal cir- cuit. in case of current input: shunt resistor need to be connected to the analog input terminal. (250 ? shunt resistor is optional item) (2) thermocouple (option) types and measurable ranges: * see table 2. input accuracy: 0.2% fs 1 digit [note]b type: 5% between 0 to 400?c s and r type: 1% between 0 to 500?c all type of tc: 5% under ?00?c reference junction compensation error: 1.0 c (provided measurable range is 50 c and higher) [note]reference junction compensa- tion resistor is connected at external input terminal in case of thermo- couple input is ordered. input accuracy guarantee range: 5% to 105% of input range. input resistance: 1 m ? or more ? llowable signal source resistance: 100 ? or less (zener barrier connection unallowable) influence by signal source resistance: about 0.25 v/ ? influence by ambient temperature: 0.2% fs/10 c 1 c or less. influence by power supply fluctuation: 0.2% fs 1?c or less burnout detection: provided isolation: isolated from internal circuit. (3) resistance bulb (option) types and measurable ranges: * see table 2. input accuracy: 0.2% fs 1 digit input accuracy guarantee range: -5% to 105% of input range allowable wiring resistance: 10 ? or less per wire, provided wiring resis- tance must be equal among 3 wires (ze- ner barrier connection unallowable) influence by ambient tempera- ture: 0.2% fs/10?c or less. influence by power supply fluctuation: 0.2% fs or less burnout detection: provided isolation: isolated from internal circuit. [note] fs: full span. ?sampling period : 100 ms 2-2 digital input signal ?number of inputs : 10 inputs ?electrical specifications : no-voltage contact or transistor contact on/0 v, off/24 v, on current/about 8 ma isolated from the internal circuit by photocoupler. not isolated between each digital input and output. ?contact rating : 30 v dc, 10 ma or more ?signal judgment : no-voltage contact contact resistance; 200 ? or less at on, 100 k ? or more at off : transistor contact 1 v max at on., leakage current 100 a max. at off
3 3. output signals performance under reference condition (23 2?c, 55 10%rh, 100 v to 240 v ac, 50/60 hz power supply frequency or 24 v dc power supply voltage, free from vibration and the effect of external noise) 3-1 analog output signal (1) control output ?number of outputs : selectable among 1, 2 and 4 outputs ?output signal :4 to 20 ma dc ?output accuracy : 0.2% fs ?load resistance : 600 ? or less ?output accuracy guarantee range :2 to 22 ma dc ?influence by ambient temperature : 0.2% fs/10?c or less ?influence by power supply fluctuation : 0.2% fs or less ?isolation : non-isolated from internal circuit (2) auxiliary analog output ?number of outputs: screw terminal ; 5 outputs compression terminal ; 4 outputs ? types of signal : selectable among 0 to 5 v dc, 1 to 5 v dc and 0 to 10 v dc initial set before delivery: 1 to 5 v dc ?output accuracy : 0.1% fs ?load resistance : 15 k ? or more ?output guarantee range :1 to 5 vdc : ?2.5% to 112.5% :0 to 5 vdc : 0% to 112.5% :0 to 10vdc : 0% to 105% ?influence by power supply fluctuation : 0.1% fs or less ?solation : non-isolated from internal circuit 3-2 digital output signal ?number of outputs :10 outputs ?electrical specifications : transistor open collector 1 v max. at on, 10 a max at off. isolated from the internal circuit by photocoupler. not isolated between each digital input and output. ?output rating : 30 v dc, 100 ma max. (resistive load) 3-3 fault output signal (terminal symbol flt) ?number of outputs :1 output ?electrical specifications : transistor open collector 1 v max. at on, 10 a max at off. isolated from the internal circuit by photocoupler. not isolated between each digital input and output. ?output rating : 30 v dc, 100 ma max. (resistive load) 4. display ?display unit : 16 colors graphic liquid crystal display, with cfl back light and contrast adjust function. ?contents of display : menu : loop panel (1, 2, 4 and 8 loops) bar graph display, digital display, etc. [note] the term "loop" hereby indicates the number of control blocks. it does not mean the number of control out puts. : tuning screen : trend screen (max. 8 screens) : alarm and alarm historical screen : analog input/output and digital input/ output indication screen : wafer connection screen : parameter setting screen 5. setting and operation (1) set point setting method ?setting key : up key/down key ?setting speed :a bout 40 s/fs ?setting resolution : 0.05% fs/each key press (2) control output operation method ?operation key : up key, down key and high-speed key ?operation speed : about 40 s/fs (usual), about 8 s/fs (high speed) (3) operation mode ?kinds of operation mode :c (or r), a, m and hm [ not e] c : cascade mode (operation according to remote set point) r : remote mode (operation according to remote set point) a : auto mode (operation according to the local set point) m :m anual mode (control output to be manually operated by operator) hm : hard manual mode (the mode in which operation is performed with a backup operating device) [remark] c and r have different nameplates, while operation is the same. ?setting method : selectable from the followings by specifieing the code symbols. c - a - m a - m r - a - m ?changeover : balance bumpless changeover from auto to remote and from auto to cascade balanceless bumpless in other changeover [ not e] balance bumpless changeover is a method where each setting value needs to be bal- anced by operator himself at the time of changeover. balanceless bumpless changeover is a method where each setting value is auto- matically balanced by the controller at the time of changeover.
pda2 4 (4) security ?method : setting of a password ?password : settable in 4 numerals (within 0000 to ffff) initial set before delivery: 0000 ?contents of security : inhibition of parameter setting (5) other setting items ?tag name : settable in up to 8 characters usable characters; alphabes, numerals, symboles such as +, ?, * ,etc. 6. power supply ?voltage rating : 100 v to 240 v ac 50/60 hz/24 v dc [accoding to code symbols] ?allowable range : 85 v to 264 v ac/20 v to 30 v dc [ac- cording to code symbols] ?frequency : 47 to 63 hz ?power consumption : 60 va or less (100 v to 240 v ac) : 30 w or less (24 v dc) power supply output voltage (terminal symbol vp and pc) : 20 v to 30 v dc, max. 40 ma 7. general performance and characteristics ?insulation resistance : 500 v dc, 50 m ? or more. ?dielectric strength : 2,000 v ac for 1 minute between power terminal and ground terminal in case of 100 v to 240 v ac power supply : 500 v ac for 1 minute between power terminal and ground terminal in case of 24 v dc power supply. : 500 v ac for 1 minute between signal, communication terminals and ground terminal ?rush current : 60 a or less. (100 v ac to 240 v ac power supply) ?clock : set and display year, month, day, hour, minute, second accuracy : 100 ppm except of time lag shorter than 1 s / power on / off ac- tion. ?memory backup :p rotection by lithium battery. (expected battery life is about 2 years under room temperature) parameter and program are stored non- volatile memory. 8. operating and storage conditions ?location : indoor ?operating temperature :0 to 50?c :0 to 40 c in case of multiple mounting ( temperature change rate : max. 10?c / h ) ?transport and storage temperature : -20 to 70?c ( temprature change rate : max. 20?c / h ) ?operating humidity :5 to 90% rh, condensation unallowable ?transport and storage humidity :5 to 95% rh, condensation unallowable ?operating continuous vibration : 4.9 m/s 2 or less ?transport and storage shock : fall of 60cm max. in packed status 9. power failure and restart function ?permissible duration of momentary power failure : 20 ms at 90 v ac (100 v to 240 v ac only) in the case of 24v dc, it is recom- mended to avoid power failure problem that system power supply unit with per- missible duration of momentary power failure of 20 ms or more (pxj, for ex- ample) is used. ?behavior at power failure detection :c ontrol stops at detection of power fail- ure. ?power recovery mode : selectable initial start and continuous start 10. self-diagnosis ?control and computation circuit failure :m onitoring with watchdog timer ?input signal failure : voltage/current input monitoring of range over : thermocouple and resistance bulb monitoring of disconnection ?control output signal failure : monitoring of disconnection by read back check ?behavior at failure : flt is indicated, flt lamp lights, flt output signal turns on, control stops and control output is held. 11. structure ?enclosure : plastic (material: pc-abs) ?finish color : front frame and enclosure both gray ?flame resistance :u l94v-0 ?protection : front face; ip54 (display unit and operation key) ?external dimensions (w x h x d) screw terminal type : 72 x 144 x 272 mm compression terminal type : 72 x 144 x 280 mm ?mass : 1.9 kg or less ?mounting method : flush on indoor panel vertical mounting as standard tilted mounting allowed within back- ward angle 0 to 45 . 90 to 45 ?external terminal : screw terminal type (m3.5) or com- pression terminal type (by the code symbols)
5 12. backup function (option) ?method : with backup operation unit ?number of control outputs : 1, 2 or 4 outputs selectable. ?output signal :4 to 20 ma dc ?indication : control output indication of each loop (ma indication) ?indicator : 21-segment led ?indication changeover : changeable to each loop by loop selec- tion key loop no. indicated by 1-digit led ?operation key : control output up, control output down, loop selection ?operation resolution :5% ?backup changeover : changeover has been made by the hm (hard manual) switch. however, changeover cannot be made when the backup operation unit is faulty. : in all loops, changeover to the hm mode is blanceless and bumpless. 13. communications (option) 13-1 t-link interface (option) communication behavier : master or slave master communication : connecting to cpu capsule : i/o transmission ; 4 / 8 / 16-word inputs and / or outputs :m essage transmission ; single element slave communication : connecting to i/o equipments connectable equipments ; ftls, pna, pyh : i/o transmission only input / output area is 100 words (mes- sage transmission, transmisson be- tween master stations, loader transmis- sion and duplex transmission are not available.) common items for both master communication and slave communication : wiring system ; multi-drop : communication speed ; 500 kbps :c ommunication distance; max. 500 m in total (for master), max. 50 m in total (for slave) : isolation ; not isolated from internal cir- cuit : terminator ; 100 ? (optional item) 13-2 loader interface communication protocol : based on modbus protocol physical specification : rs232c communication distance : max. 3 m 14. memory card interface (option) ?specification : compact flash (based on cfa) ?compatible memory card :5 v flash memory card capacity 4, 20 and 32 mb ?application :p rocess data logging (32 points or less) ?saving period :1 s min. ?data storage capacity memory card capacity data storge 4mb about 180 thousand data 20mb about 900 thousand data 32mb about 1.35 million data [remark] values of 4 points are recorded si- multaneously by one data. [ not e] the data of max. 16 points (4 screens) can be storaged at stor- age time as 1 s. ?format method : dependent on this controller ?data readout : readout by pc using pcmcia card slot ?recommended memory card :m ade by sandisk corporation sandisk compact flash memory card is standardized and on the market. models ; sdcfb-4-101-00 (4mb) sdcfb-20-101-00 (20mb) sdcfb-32-101-00 (32mb) 15. standards under conformity (1) general safety :i ec 1010-1 (1990) en 61010-1 (1993) (2) emc : emission en 50081-2 (1994) immunity en 50082-2 (1995) 16. configuration software 16-1 programming loader software this software is installed on the cd-rom form instruction manual (pdzq1001) supplied with the main unit. communication cable (pdzl1001) is optionally available. ?wafer connection can be entered, edited, uploaded and downloaded. ?operation parameter can be entered, edited, uploaded and downloaded. 16-2 recommended personal computer system ?hardware : dos/v machine, pentium 100 mhz or higher free hard disk capacity 40 mb or more, memory capacity 32 mb or more ?operating system : microsoft windows 98 se/2000/xp japanese
pda2 6 wa fer name kinds outline primary pid carries out computation on the primary loop. 9 5 2 8 1 1 5 6 8 1 1 secondary pid carries out computation on the secondary loop. gain schedule outputs the pid parameter corresponding to input 1 according to the gain schedule table. bit concatevate outputs digital data as word data to an external expansion i/o. bit slicing slices the digital data acquired as word data from an external expansion i/o into each bit. encoder encodes an input signal into a binary code. sawtooth wave generator generates a sawtooth wave with a slope entered for each cycle time. bcd converts bcd data into binary data and binary data into bcd data. logical operation arithmetic operation te mperature/pressure compensation carries out and, or, not, xor and a combination of these logical operations. carries out a combination of addition, subtraction, multiplication and division. carries out temperature and pressure compensation through use of differential pressure, compensated pressure, proper temperature. 4 1 1 program control flip-flop pulse width integration ti me schedule control by step or polygonal line approximation with 7 segments. rs flip-flop. adds the change of input at each basic cycle to the previous integration value. 7 linearize carries out segmented-line approximation with 15-segmented- line function. 2 1 1 1 1 1 1 1 3 1 ramp function analog averaging analog integration selector changeover timer absolute value/sign inversion square root extraction lead,lag limiter compares two input values,and provides high output(large one), low output(small one),and result of judgement on large/small. selects input or output via a switch function.analog hold circuit also provided. outputs on-delay,off-delay timer signal via start of input signal according to timer setting. carries out absolute value processing on input and outputs the result.also judges the sign(positive,negative)of input value and outputs the result. extracts square root of input value and outputs the result.low input cutoff function equipped. carries out lead/lag operation on the input and outputs the results. used as analog filter function and for various compensations. limits the input within the range of high/low limit settings,and outputs the result.also outputs high/low limit alarm signal. outputs signal which changes...in ramp from toward target value at the set full scale time.there are two of these wafers...in minute unit and hour unit. carries out sequential integration on input data,calculates the average value at each averaging time, and otuputs the result. integrates the value obtained by multiplying the input data by a proportional constant,and outputs the result. outputs on-off signal with hysteresis. indicator 1 1 1 1 2 1 6 1 1 8 1 pulse generation dead band pulse no.counter pulse no.output decoder running average sample & hold dead time on-off alarm outputs a pulse at the set time interval. adds dead band compensation to the input and outputs the result. detects rise of pulse and counts the number of pulses. integrates the input signal and converts it to number of pulses for output. decodes 2-bit pure binary input and outputs it to 4 terminals. calculates ranning average of input data and outputs the result. holds the input value according to sample signal(0/1)and continues the output. usable for dead time compensation control etc.data sampling can be done in 1 sec or 1 min units. compares the input and set value and outputs the judgment result. indicate input data on the front display (using 3 bar-graph display) palse width modurator 1 performs output processing in time proportional pid control. a variety of applications are possible through combination of wafers. wa fer name kinds outline table 1 list of wafers
7 table 2 list of thermocouple and resistance bulb measurable range thermocouple j 01 00 0.0~400.0 j0 1 0.0~800.0 k0 2 0.0~400.0 k0 3 0.0~800.0 k0 4 0.0~1200.0 r0 5 0.0~1600.0 b0 6 0.0~1800.0 t07- 200.0 ~ 200.0 t08- 150.0 ~ 400.0 e0 9 0.0~800.0 e10- 200.0 ~ 800.0 s 11 0.0~1600.0 n1 2 0.0~1300.0 u13- 200.0 ~ 400.0 wre5-26 14 0.0~2300.0 pl 2 15 0.0~1300.0 resistance bulb pt100 00 00 0.0~150.0 01 0.0~300.0 02 0.0~500.0 03 0.0~600.0 04 -50.0~100.0 05 - 100.0 ~ 200.0 06 - 200.0~600.0 07 - 200.0~850.0 resistance bulb jpt100 00 08 0.0~150.0 09 0.0~300.0 10 0.0~500.0 11 0.0~600.0 12 -50.0~100.0 13 - 100.0~200.0 14 - 200.0~600.0 input type code input range code measurable range?c input signal scope of delivery controller, panel mounting bracket, instruction manual (depend on code symbols) optional items type specification available unit item (note 2) these cables are used for t-link and modbus ? . length needs to be specified. (note 3) the instruction manual and introductory guide both in japanese and english, and programming loader software (in japanese) are included. (note 4) this is the improved mounting bracket adopted from pda-2. refer to the outline diagram for shape and dimensions. (note 1) this connector is reguired for using the controll output 3 and 4 or digital input / output with the screw terminal type. terminator for communication (100 ? ) 34-pin multiple connector shunt resistor (250 ? ) communication cable for configuration software communication cable (note2) for screw terminal, from pda to pda for screw terminal, from pda to plc for screw terminal, from pda to pc for compression terminal, from pda to pda for compression terminal, from pda to plc for compression terminal, from pda to pc replacing case compact controller m (cc-m) instruction manual in book form (in japanese) compact controller m (cc-m) instruction manual in book form (in english) compact controller m (cc-m) introductory guide in book form (in japanese) compact controller m (cc-m) introductory guide in book form (in english) instruction manual on cd-rom (in japanese and english) (note3) mounting bracket (note4) pdzr1001 for screw terminal 1 pdzr2001 for compression terminal 1 pdzc1001 solder type straight terminal 1 pdzc2001 solder type right angle terminal 1 pdzc3001 solderless type straight terminal 1 pdzc4001 solderless type right angle terminal 1 pdzs1001 for screw terminal 1 pdzs2001 for compression terminal 1 pdzl1001 commonly usable cable 1 for configuration software (3m length) pdzk1xx1 m3.5 solderless terminals 1 at both ends pdzk2xx1 m3.5 solderless terminals 1 at both ends pdzk3xx1 9-pin connector at 1 pc side end pdzk4xx1 with compression 1 terminal at both ends pdzk5xx1 with m3.5 solderless 1 terminal on plc side pdzk6xx1 9-pin connector on pc side 1 pdze1002 for replasing cc-f 1 pdzx1001 instruction manual in 1 book form pdzx2001 instruction manual in 1 book form pdzx3001 instruction manual in 1 book form pdzx4001 instruction manual in 1 book form pdzq1001 instruction manual on 1 cd-rom pdza1001 improved mounting 1 bracket (note1) block diagram of electrical isolation (note) the communication unit is not isolated from the ai/ao unit when using t-link. (note) power supply ground pv1 pv2 t-link (slave) di1 to di10 solid line shows isolation from the other units or circuits. do1 to do10 ai1 to ai6 mi1 to mi14 ao1 to ao5 t-link (master) power supply unit ground tc or rtd input unit tc or rtd input unit communication unit di / do unit ai / ao unit
pda2 8 code symbols da 2 p-- controller function <4th digit code> programmable type note 1 2 12345678 910111213 1415 number of control loops <5th digit code> note 2 1 loop (1 control output) 2 loops (2 control outputs) 4 loops (4 control outputs) 1 2 4 input signal <7th digit code> 1 to 5 v dc note 3 thermocouple note 4 resistance bulb pt100 note 4 resistance bulb jpt100 note 4 a c d e external terminal <6th digit code> m3.5 screw terminal compression terminal 1 2 backup operation unit <11th digit code> without for 1 control output, 100 to 240 v ac for 2 control outputs, 100 to 240 v ac for 4 control outputs, 100 to 240 v ac for 1 control output, 24 v dc for 2 control outputs, 24 v dc for 4 control outputs, 24 v dc y a b c d e f programming method <14th digit code> wafer connection method 1 communicatioin / memory card interface <12th digit code> (slave) (master) (memory card interface) note5 note6 without without without without without with t-link without without t-link t-link without t-link without with t-link t-link with y m a b s t instruction manual <13th digit code> without instruction manual on cd-rom (in japanese and english) note 9 factory configuration<15th digit code> without wafer connection note 7 with up to 48 wafer connection note 8 with more than 49 wafer connection note 8 y c 0 8 9 power supply voltage <9th digit code> 100v to 240v ac (usable range 85v to 264v ac) 50 / 60hz 24v dc (usable range 20 to 30v dc) note 1) control and computation function could be done by wafer connection. note 2) control loop means the number of control output. note 3) for current input, a shunt resistor is used for conversion into voltage. shunt resistor is optional item. note 4) thermocouple and resistance bulb input are opitons. allowable up to 2 points. the remaining input will be 1 to 5 v dc. note 5) communication cable and terminator are optional items. note 6) recommended maker: sandisk corporation. note 7) in this case, wafer connection programming should be made by user. connection tool (programming loader) is optional item. note 8) wafer connection specification sheets need to be prepared and submitted by user to fuji. input signal and measurable range initial set before delibvery is as follows. for specification of voltage input, scale is 0.00 to 100.00% for specification of thermocouple, k, 0.0 to 400.0?c. for specification of resistance bulb, pt and jpt are 0.0 to 150.0?c. note 9) this cd-rom contains the programming loader written in japanese. however, the communication cable (pdzl1001) is separately available. the relevant manual is stored in the pdf file format. for reading the manual, adobe acrobat reader is required. the cd-rom also contains the acrobat reader setup program. a b operation mode <10th digit code> cascade-auto-manual changeable type auto-manual changeable type remote-auto-manual changeable type c a r description
9 functional diagram pc analog output configuration software max.4 loops control and computation wafer region memory card (option) communication t-link or modbus (option) communication t-link (option) loop 1 loop 2 loop 3 loop 4 2nd pid 1st pid digital input screw terminal or compression terminal multiple connector only for screw terminal digital output thermocople / resistance bulb (option) analog input control output back up operation unit (option) modbus ? (rs232c) micrex t-link to master ftls/ pyh t-link to slave (note 1) the numbers of analog input and auxiliary analog output differ depending on external terminals. (note 1) (note 1)
pda2 10 for mounting one unit for mounting multiple ??units 68 +0.7 0 138 +1 0 250 or more (72.2n-4) +1 0 138 +1 0 250 or more number of n 2 n ; q'ty panel cutout dimensions outline diagram (unit : mm) screw terminal type panel terminal cover cover bracket mounting bracket panel thickness 8 mm or less 20 144 72 280 21.6 137.5 100min. 67.5 note) the distance between other instruments and low end of pda shall be more than 100mm. note) the distance between other instruments and low end of pda shall be more than 100mm. 144 72 272 134 21.6 137.5 100min. 20 panel terminal cover cover bracket mounting bracket panel thickness 8 mm or less 67.5 compression terminal type
11 mounting bracket 50 205 160 16 external connection diagram screw terminal type ????m3.5 screw terminal section screw terminal type ????multipul terminal section instrument power supply 100 to 240v ac grounding voltage output t-link downward communication t-link upward communication 24v external supply (common) manipulated output 1 manipulated output 2 24v external supply (+) voltage input voltage input resistance bulb input thermocouple input process value input 1 process value input 2 51 52 53 54 55 56 57 58 59 60 61 62 63 64 ao1 ao2 ao3 ao4 ao5 sc sc sc mod+ mod- vst1 pc pcd g n/- rcj (+) 24v supply for dio (-) (+) (-) (+) (-) pcd vpd instrument power supply 24v dc 71 72 73 74 75 76 77 78 79 80 81 82 83 ai1 ai2 ai3 ai4 ai5 sc vp mi+1 mi-1 mi+2 mi-2 vpd l/+ 11 12 13 14 15 16 i+1 i-1 io1 i+2 i-2 io2 31 32 33 34 35 36 37 flt do1 di1 di2 vst2 t1 t2 (+) (-) (com) pcd vpd pcd rcj (+) (-) (-) (+) (com) b b a b b a 1 2 3 4 5 6 7 8 9 10 11 12 mi+3 mi-3 mi+4 mi-4 ao1 ao2 sc ai1 ai2 ai3 ai4 pcd 13 14 15 16 17 18 19 20 21 22 di1 di2 di3 di4 di5 di10 di6 di7 di8 di9 23 24 25 26 27 28 29 30 31 32 33 34 do1 do2 do3 do4 do5 do6 vpd do7 do8 do9 do10 pcd multipul connector
pda2 [note] windows ? is the registered trade mark of microsoft corporation. [note] modbus ? is the registered trade mark of gould modicon. [note] compact flash ? is the registered trade mark of sandisk corporation. [note] pentium ? is the registered trade mark of lntel corporation. [note] adobe ? and acrobat ? are trademarks of adobe systems incorporated. information in this catalog is subject to change without notice. printed in japan head office 6-17, sanbancho, chiyoda-ku, tokyo 102-0075, japan http://www.fesys.co.jp/eng sales div. international sales dept. no.1, fuji-machi, hino-city, tokyo, 191-8502 japan phone: 81-42-585-6201, 6202 fax: 81-42-585-6187 http: //www.fic-net.jp/eng caution on safety *before using this product, be sure to read its instruction manual in advance. external connection diagram compression terminal type 43 44 45 46 47 48 49 50 51 52 53 54 55 56 mi+1 mi-1 ao1 sc ao2 ao3 sc ao4 flt do1 do2 do3 do4 57 58 59 60 61 62 63 64 65 66 67 do5 di1 dio-com di2 di3 dio-com di4 di5 i+1 io1 rcj-1 rcj (+) vpd vpd pcd (-) (+) (-) i-1 a b b 22 23 24 25 26 27 28 29 30 31 32 33 34 35 mi+2 manipulated output 2 manipulated output 3 manipulated output 4 mi-2 mi+3 mi-3 mi+4 mi-4 do6 do7 do8 dio-com di6 di7 dio-com 36 37 38 39 40 41 42 di8 opt+ opt- com i+2 io2 rcj-2 i-2 rcj (+) (+) pcd (-) process value input 2 a b b (-) (+) (-) (com) t -link downloading process value input 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 ai1 sc ai2 ai3 sc ai4 ai5 sc ai6 sc vp pc di9 15 16 17 18 19 20 21 di10 do9 do10 mod+ mod- com vpd pcd pcd vo ltage input vo ltage output (+) (-) 24 v external supply (+) (-) (com) t -link uploading 24 v supply for dio vo ltage input resistance bulb input thermo- couple input vo ltage input resistance bulb input thermo- couple input manipulated output 1 g n/- l/+ instrument power supply 100 to 240vac instrument power supply 24vdc grounding


▲Up To Search▲   

 